Products Description
Our automatic transformer cooling controller handles dual-power transfer, automatic cooler rotation, load-start input, manual override, and fault outputs. Working and auxiliary coolers rotate at the stated interval to share operating time.
Technical Principle
Temperature, load, oil-flow, fan, and pump feedback are collected by the controller. Programmed logic starts, stops, rotates, and transfers cooling groups according to configured thresholds while issuing fault alarms and recording operating status.

Product Features
The automatic transformer cooling controller applies a defined temperature sequence without continuous operator action. Thirty-day rotation shares operating hours between main and auxiliary cooler groups. Dual-power transfer preserves control when the selected source fails. Dedicated fault outputs give the station clear indications for protection and alarm handling.
Operating Conditions
Install the product in a clean, ventilated location without corrosive gas, conductive dust, water ingress, severe vibration, or strong impact. Provide reliable protective grounding, maintain the required electrical clearances, and use the rated auxiliary power supply. Confirm ambient temperature, humidity, altitude, enclosure protection, cable routing, and communication conditions before production and installation.

Product Parameters
|
Parameter |
Details |
|
Control modes |
Manual, automatic, and remote |
|
Auxiliary-cooler start |
55°C |
|
Auxiliary-cooler stop |
Below 45°C |
|
Cooler rotation interval |
30 days |
|
Load-start contact |
Normally open; closed starts all coolers, open stops them |
|
Dual-power function |
Automatic transfer to the alternate source and return after recovery |
|
Full-stop trip with 75°C signal |
20-minute delay |
|
Full-stop trip without 75°C signal |
1-hour delay |
|
Fault outputs |
Cooler fault, all-coolers stopped, PLC fault, supply fault, and DC control-supply fault |
|
Cabinet environment |
-25°C to +70°C; ≤95% RH at 25°C; IP55 |
Product Advantages
- The automatic transformer cooling controller applies a defined temperature sequence without continuous operator action.
- Thirty-day rotation shares operating hours between main and auxiliary cooler groups.
- Dual-power transfer preserves control when the selected source fails.
- Dedicated fault outputs give the station clear indications for protection and alarm handling.
Main Applications
The automatic transformer cooling controller is used for transformer fan and oil-pump groups that need automatic start, rotation, and standby transfer.
It supports new cooling cabinets and project-specific control upgrades based on approved logic.
The controller serves utility substations, generation plants, and industrial transformer systems.
Components
|
Part |
Function |
|
Programmable controller |
Executes temperature, load, rotation, and fault logic. |
|
Dual-power switching circuit |
Transfers control power between two sources. |
|
Motor-control outputs |
Start or stop working, auxiliary, and standby coolers. |
|
Alarm and trip outputs |
Report cooler, PLC, power, and all-stop conditions. |
FAQ
Q: What information is needed for model selection?
A: Provide the cooler quantity, main and auxiliary grouping, temperature contacts, load input, and trip philosophy.
Q: What should be checked before installation?
A: Verify dual-power phasing, motor interlocks, contact logic, alarm destinations, manual controls, and emergency operation.
Q: How can the device or system be integrated?
A: Hardwired status, alarm, and control signals connect the controller with the transformer and station circuits.
Q: Which options should be confirmed before production?
A: Confirm thresholds, time delays, rotation interval, cooler grouping, output contacts, and remote-control requirements.
Hot Tags: automatic transformer cooling controller, China automatic transformer cooling controller manufacturers, suppliers, factory