Products Description
Our transformer cooling automation system collects transformer temperature, load, power, and motor status before applying programmable cooler logic. Dual bus sections, modular I/O, and communication interfaces support dependable operation.
Technical Principle
Temperature, load, oil-flow, fan, and pump feedback are collected by the controller. Programmed logic starts, stops, rotates, and transfers cooling groups according to configured thresholds while issuing fault alarms and recording operating status.

Product Features
The transformer cooling automation system uses programmable logic to balance working, auxiliary, and standby cooler groups. Staggered starts reduce simultaneous motor inrush and allow timed group sequencing. Independent bus sections preserve control capability if one section has a fault. Expandable I/O and networking support future signals and distributed supervision.
Operating Conditions
The product shall be installed and operated within the ratings stated in the technical parameters. Key site requirements include: altitude ≤2500 m. Keep the installation area clean, adequately ventilated, free from corrosive gas and severe vibration, and provide the specified grounding, clearance, and power quality.

Product Parameters
|
Parameter |
Details |
|
Controller |
PLC-based intelligent control |
|
Display |
7-inch color industrial touch screen |
|
Display interfaces |
USB and Ethernet |
|
Operating modes |
Manual, automatic, and remote |
|
Bus arrangement |
Two independent bus sections |
|
Protection functions |
Overcurrent, phase loss, power-supply, and system-fault protection |
|
Outdoor environment |
-25°C to +70°C; ≤95% RH at 25°C; altitude ≤2500 m |
|
Cabinet protection |
IP55 |
|
Cabinet construction |
≥2.0 mm 1Cr18Ni9Ti stainless steel |
|
EMC references |
EN 61131-2/EN 61000-6-2 and EN 50082-2/EN 61000-6-4 |
Product Advantages
- The transformer cooling automation system uses programmable logic to balance working, auxiliary, and standby cooler groups.
- Staggered starts reduce simultaneous motor inrush and allow timed group sequencing.
- Independent bus sections preserve control capability if one section has a fault.
- Expandable I/O and networking support future signals and distributed supervision.
Main Applications
The transformer cooling automation system is used for intelligent substations and power plants that require automated transformer cooling management.
It is suitable for multi-group fan and pump systems with standby rotation and remote control.
The platform supports local visualization, alarm history, and control-room supervision.
Components
|
Part |
Function |
|
PLC and I/O |
Acquire signals and execute programmable cooler logic. |
|
Touch screen |
Displays status, alarms, parameters, and operating controls. |
|
Dual power and bus circuits |
Provide independent power distribution for cooler groups. |
|
Network interfaces |
Connect displays, printers, other PLCs, or the station computer. |
FAQ
Q: What information is needed for model selection?
A: Provide the cooler-group schedule, motor ratings, temperature and load contacts, standby policy, and remote signals.
Q: What should be checked before installation?
A: Verify PLC I/O lists, power separation, motor protection, field interlocks, network addressing, and acceptance logic.
Q: How can the device or system be integrated?
A: The PLC can communicate with displays, printers, other PLCs, or a supervisory computer through selected interfaces.
Q: Which options should be confirmed before production?
A: Confirm PLC and HMI brand, I/O reserve, networking, alarm list, dual-bus design, and programmed sequence.
Hot Tags: transformer cooling automation system, China transformer cooling automation system manufacturers, suppliers, factory